For 24V ac/dc operation, solid-state or relay inputs• Monitors a wide variety of safety and non-safety input devices:• Optical-based safeguarding devi
WARNING: Reset Routine RequiredU.S. and international standards require that a reset routine be performed after clearing the cause of astop condition
Checkout ProceduresCAUTION: Disconnect Power Prior to CheckoutBefore performing the initial checkout procedure, make certain all power is disconnected
Periodic CheckoutThe functioning of the Safety Module and the device(s) connected to it must be verified on a regular periodic basis to ensure propero
Low Current RatingThe 5 μm gold-plated contacts allow the switching oflow current/low voltage. In these low-power applica-tions, multiple contacts can
Dimensions Certifications and StandardsEC Declaration of Conformity (DOC)Banner Engineering Corp. herewith declares that the UM-FA-9A and UM-FA-11A U
Banner Engineering Corp Limited WarrantyBanner Engineering Corp. warrants its products to be free from defects in material and workmanship for one yea
OverviewThe UM-FA-xA Universal Safety Module (or "Safety Module" or "Module" in this document) is used to increase the safety circ
Indicators and AdjustmentsThe Safety Module has indicators for input power and output relay contact status (K1 and K2); see Figure 1. Features on page
contacts rated for safety. In addition, the switches must be mounted in a "positive mode," to move/disengage the actuator from its homeposit
Electrical InstallationWARNING: Shock Hazard and Hazardous EnergyAlways disconnect power from the safety system (for example, device, module, interfac
It is recommended that in all circumstances the installation of the Safety Module and its associated safety input devices are installed toeliminate or
ResetA2(No Connection)A1S34S11S33MSC1 MSC2 MSC3S22S12S210V+24V ac/dcUM-FA-..AManual ResetDevices with relay output contactsDevices with positive-openi
Auto ResetA2A1S21S11S12S220VUM-FA-..ASee Interfacing MSCsWARNINGMSC1 MSC3MSC2MSCMonitorContactsorJumperS33S34+24V ac/dc+24V ac/dcDevices with relay ou
**L2MSC1MSC2MachineMaster StopControl Elements*Arc suppressors (see WARNING)K1A6A max.6A max.6A max.K2AK1BK2BK1CK2C*MSC313 1423 2433 34L1MachineContr