Vue de la page 0
Datasheet
Long-range ultrasonic sensors with TEACH-mode programming
Fast, easy-to-use TEACH-Mode programming; no potentiometer adjustments
Scalable output automatically distributes the output signal over the width of the
programmed sensing window
Minimum and Maximum window limits can be adjusted independently
Selectable 0 to 10 V dc or 4 to 20 mA output, selected via DIP switch
Access to bank of 8 DIP switches through sealed cover for superior user
functionality
Rugged encapsulated design for harsh environments
Unique housing design allows for multiple mounting configurations
Choose models with integral 2 m (6.5 ft) or 9 m (30 ft), or with Mini-style or
Euro-style quick-disconnect fitting
Wide operating range of –20 °C to 70 °C (–4 °F to 158 °F)
Temperature compensation
Programmable for either positive or negative output slope
Models
1
Sensing Range Cable
2
Supply
Voltage
Output
QT50ULB
200 mm to 8 m (8 inches to
26 feet)
5-wire, 2 m (6.5 ft) cable
10 to 30 V dc
Selectable: 0 to 10 V dc or 4 to 20
mA
QT50ULBQ 5-pin Mini-style QD
QT50ULBQ6 5-pin Euro-style QD
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to
serious injury or death. This device does not include the self-checking redundant circuitry necessary
to allow its use in personnel safety applications. A sensor failure or malfunction can cause either an
energized or de-energized sensor output condition.
Principles of Operation
Ultrasonic sensors emit one or multiple pulses of ultrasonic energy, which travel through the air at the speed of sound. A
portion of this energy reflects off the target and travels back to the sensor. The sensor measures the total time required
for the energy to reach the target and return to the sensor. The distance to the object is then calculated using the
following formula: D = ct ÷ 2
D = distance from the sensor to the target
c = speed of sound in air
t = transit time for the ultrasonic pulse
To improve accuracy, an ultrasonic sensor may average the results of several pulses before outputting a new value.
Temperature Effects
The speed of sound is dependent upon the composition, pressure and temperature of the gas in which it is traveling. For
most ultrasonic applications, the composition and pressure of the gas are relatively fixed, while the temperature may
fluctuate.
In air, the speed of sound varies with temperature according to the following approximation:
1
Information about discrete-output models is available on Banner’s website: www.bannerengineering.com.
2
To order the 9 m cable models, add the suffix “w/30” to the model number of a cabled sensor (e.g., QT50ULB w/30). Models with
a QD connector require a mating cable.
U-GAGE QT50ULB Series Sensors with
Analog Output
Original Document
70137 Rev. B
4 April 2014
70137
Vue de la page 0
1 2 3 4 5 6 ... 10 11

Résumé du contenu

Page 1 - Analog Output

DatasheetLong-range ultrasonic sensors with TEACH-mode programming• Fast, easy-to-use TEACH-Mode programming; no potentiometer adjustments• Scalable o

Page 2 - Configuration

Accessories5-Pin Mini-Style Cordsets with ShieldModel Length Style Dimensions Pinout (Female)MBCC2-506 1.83 m (6 ft)Straight7/8-16UN-2Bø 28 mm max.(1.

Page 3

This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NOEVENT SHALL BANNER ENGINEERING C

Page 4 - General Notes on Programming

In metricunits:Cm/s = 20 √273 + TC In English units: ft/s = 49 √460 + TFCCm/s = speed of sound in meters per second Cft/s = speed of sound in feet p

Page 5

Switch Function SettingsOFF = Hold Mode3 Min-Max ON = Default to maximum output value on loss of echoOFF* = Default to minimum output value on loss of

Page 6 - Push Button Lockout

Switches 5 and 6 are used to set the speed of the output response. The four values for response speed relate to thenumber of sensing cycles over which

Page 7 - Status Indicators

Teaching Minimum and Maximum LimitsThe Min and Max Analog limits are independent. To readjust either limit, it is necessary to follow the teach proced

Page 8 - Dimensions

Remote Line Method (0.04 s < T < 0.8 s)Step Action Result1 Position the target at the location where the midpoint of thewindow should be.Min and

Page 9 - Specifications

Status IndicatorsMinMaxMinPower Signal Power Signal Power Signal Power SignalMaxMinMaxMinMaxMinimumOperatingRangeMinimumAnalogSetp

Page 10 - Accessories

WiringIntegral Cable Model Quick-Disconnect Model (5-pinMini-style)Quick-Disconnect Model (5-pinEuro-style)−4513210–30 V dcRemote Teach0–2 V dc4–20 mA

Page 11

SpecificationsSupply Voltage and Current10 to 30 V dc (10% maximum ripple)100 mA max at 10 V, 40 mA max at 30 V (exclusive of load)Sensing Range200 mm