Model ES-UA-5A for 12-24V dc/115 ac operation; model ES-VA-5A for 12-24V dc/230 ac operationOriginal Instructions• Monitors emergency stop devices, su
tions are taken to attenuate possible overvoltage situations in the supply voltage. The Module can be used in an Overvoltage Category IIIenvironment (
2. Ensure the safety device is in a STOP or "open-contact" state (e.g., actuate the E-stop switch to open its contacts).3. Apply power to th
Pollution Degree2Relay OutputsRelay Outputs4 normally open (N.O.) output channels and 1normally closed (N.C.) auxiliary outputContacts: AgNi, 5 μm gol
Both outputs are protected against short circuits.Output at Y32 monitors state of outputs – conducts (output high)when both K1 and K2 are energized.Ou
84 mm(3.3")45 mm(1.8")118.0 mm(4.6")Figure 6. Dimensions in Millimeters (Inches)TroubleshootingModule will not resetIndicator Status Po
FaultIndicator Status Possible Causes and SolutionsPower LED ONFault LED ON*Ch1 and Ch2 LED flashing alternatelyInput concurrency fault: Both inputs d
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (IN-CLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MER
ANSI B11.19 Performance Criteria for SafeguardingContact: Safety Director, AMT – The Association for Manufacturing Technology, 7901 Westpark Drive, Mc
In the United States, the typical level of safety circuit integrity is called control reliability. Control reliability typically incorporates redundan
• Mounting points, including support points, must be rigid.• The rope should be free of friction at all supports. Pulleys are recommended.WARNING: Eme
Safety Input Device Hookup OptionsThe operation of all dual-channel hookup options is concurrent, meaning that input channel 1 and input channel 2 mus
Connection of Safety SwitchesThe Safety Module may be used to monitor safety interlockingswitches that determine the position of a guard or gate. To a
WARNING: Reset Routine RequiredU.S. and international standards require that a reset routine be performed after clearing the cause of astop condition
Wiring Drawings****MSC1E-Stop SwitchMSC3MSC2MSC Monitor Contactsor Jumper for No MonitoringMSC Monitor Contactsor Jumper for No MonitoringL2MSC1MSC2Ma
****MSC1 MSC3MSC2MSC Monitor Contactsor Jumper for No MonitoringMSC Monitor Contactsor Jumper for No MonitoringL2MachineMaster StopControl ElementsK1A